TITANEX, Nexans H07RN-F cable is a flexible, elastomer-insulated and jacketed cable with a copper core.
Advantages
- Very high flexibility.
- Very high crush resistance.
- Good resistance to chemicals, oils and vibrations
For more than 50 years, TITANEX cables have been recognised and are the guarantee of reliable installations in industrial environments (factories, construction sites, ports...) whether they are fixed or mobile such as for cranes, machine tool connections, motor power supplies...
The mechanical qualities of TITANEX cables also make them suitable
for use in event environments, such as festivals, concerts and sports
events, where the cable is exposed without protection and can be used
repeatedly.
Core temperature : 90°C
Operating voltage: 450 / 750 V mobile, 0.6 / 1 kV fixed
TITANEX
H07RN-F cables have been designed to limit the generation and spread of
fire and smoke
Reaction to fire Eca (EN 50575:2014+A1:16)
Flame retardant (IEC 60332-1, C2)
Installation
TITANEX cables can be laid in cable trays, on shelves, inside ducts
or fixed to walls, outside with or without protection. They can also be
immersed with additional mechanical protection. Additionally, they can
also be installed outdoors without protection (UV resistance).
Minimum bending radius
- Dynamic: 6 to 8 x outer diameter of the cable.
- Static: 3 x outer diameter of the cable if OD < or =12 mm, 4x if OD >12 mm.
When pulling the cable, all conductors must be equally stressed.
The tensile force must never exceed 15 N/mm² of total cross-section.
The maximum tensile force should never exceed 1000 N in total,
although the above rule may lead to higher values for large cable
cross-sections.
Markings
TITANEX 90°C n (x or G) s NEXANS CE USE<har>H07RN-F - factory n°
Made in France Y Eca N° dop
Y = year of production
n = number of conductors
s = cross-section in mm²
G = with G/Y x = without G/Y