KABEL FRC 500

FIRE RESISTANT CABLE
Kabel tahan api digunakan dalam banyak aplikasi di pabrik pengecoran dan baja, produksi kaca, industri dan di bidang militer. Kabel Tahan Api juga digunakan di area di mana jika terjadi kebakaran, semua jenis peralatan vital harus tetap beroperasi.




FRC 500
Merk                      : First Cable
Construction


Conductor                 : Stranded plain annealed copper wire to IEC-60228 class 2
Flame barrier : Glass mica tape
Insulation  : XLPE compound
Sheath : Low Smoke Zero Halogen compound, orange colour

Technical Data


Voltage rating : 300/500V
Test voltage : 2000VAC / 5 mins
Operating temp.        : -400C to 900C
Min. bending radius   : 8 x overall diameter of cable

Product performance
Fire resistant test : IEC - 60331 ; BS-6387 categories C,W & Z
Flame propagation : IEC-6332-1 ; IEC-60332-3 categories A,B,C
Oxygen density test : ASTM D2863 min. 34%
Smoke density test : IEC-61034-1&2
Halogen content test : IEC-60754-1
Acid gas emission : IEC-60754-2