Kabel tahan api digunakan dalam banyak aplikasi di pabrik pengecoran dan baja, produksi kaca, industri dan di bidang militer. Kabel Tahan Api juga digunakan di area di mana jika terjadi kebakaran, semua jenis peralatan vital harus tetap beroperasi.
Merk : First Cable
Construction
Conductor | : Stranded plain annealed copper wire to IEC-60228 class 2 |
Flame barrier | : Glass mica tape |
Insulation | : XLPE compound |
Sheath | : Low Smoke Zero Halogen compound, orange colour |
Technical Data
Voltage rating | : 300/500V |
Test voltage | : 2000VAC / 5 mins |
Operating temp. | : -400C to 900C |
Min. bending radius | : 8 x overall diameter of cable |
Product performance
Fire resistant test | : IEC - 60331 ; BS-6387 categories C,W & Z |
Flame propagation | : IEC-6332-1 ; IEC-60332-3 categories A,B,C |
Oxygen density test | : ASTM D2863 min. 34% |
Smoke density test | : IEC-61034-1&2 |
Halogen content test | : IEC-60754-1 |
Acid gas emission | : IEC-60754-2 |